Name:
ASTM F1273-91(2013) PDF
Published Date:
10/01/2013
Status:
Active
Publisher:
ASTM International
1.1 This specification provides the minimum requirements for design, construction, performance, and testing of tank vent flame arresters.
1.2 This specification is intended for flame arresters protecting systems containing vapors of flammable or combustible liquids where vapor temperatures do not exceed 60°C. The test media defined in 9.1.1 can be used except where arresters protect systems handling vapors with a maximum experimental safe gap (MESG) below 0.9 mm. Flame arresters protecting such systems must be tested with appropriate media (the same vapor or a media having a MESG no greater than the vapor). Various gases and their respective MESG are listed in Table 1.
TABLE 1 Gases and Their MESGsInflammable Gas or Vapor
Maximum Experimental
Safe Gap
mm
in.
Methane
1.170
0.046
Blast furnace gas
1.193
0.047
Propane
0.965
0.038
Butane
1.066
0.042
Pentane
1.016
0.040
Hexane
0.965
0.038
Heptane
0.965
0.038
Iso-octane
1.040
0.041
Decane
1.016
0.040
Benzene
0.99
0.039
Xylene
1.066
0.042
Cyclohexane
0.94
0.037
Acetone
1.016
0.040
Ethylene
0.71
0.028
Methyl-ethyl-ketone
1.016
0.040
Carbon monoxide
0.915
0.036
Methyl-acetate
0.990
0.039
Ethyl-acetate
1.04
0.041
Propyl-acetate
1.04
0.041
Butyl-acetate
1.016
0.040
Amyl-acetate
0.99
0.039
Methyl alcohol
0.915
0.036
Ethyl alcohol
1.016
0.040
Iso-butyl-alcohol
0.965
0.038
Butyl-alcohol (normal)
0.94
0.037
Amyl-alcohol
0.99
0.039
Ethyl-ether
0.864
0.034
Coal gas (H2 57 %)
0.482
0.019
Acetylene
| File Size : | 1 file , 84 KB |
| Note : | This product is unavailable in Russia, Ukraine, Belarus |
| Number of Pages : | 5 |
| Published : | 10/01/2013 |