In an effort to further optimize their corrosion control strategy, a Lake Michigan water utility
tested several phosphate inhibitors for their effectiveness to control lead. The objective of this
research was to show through pipe loop testing, the impact of different forms and dosages of
phosphate-based corrosion inhibitors on lead levels. Furthermore, this study investigated the
impact of seasonal temperature variations on lead levels and the role of deposition formation in
corrosion control.
Testing was completed using multiple pipe loop systems. Each loop was constructed of two 15-
foot legs of 1-inch lead service line gathered from the utility's distribution system. Water flowed
through the loops at 2 feet per second (ft/s) for 16 hours and then stagnated for 8 hours. Samples
were collected after approximately 7 hours of stagnation. Several conditions were tested over a
three year period. Overall results from the testing showed the following:
orthophosphate was more effective than polyphosphate for controlling lead levels;
orthophosphate alone was as effective as blended phosphate in controlling lead levels;
lead levels were moderately impacted by temperature and increased at higher
temperatures;
short-term variations in phosphate feed did not seem to impact lead levels;
phosphate application may result in the formation of a deposit as it combines with water
treatment chemicals, such as aluminum; and,
lead levels and phosphate doses can be optimized to meet multiple objectives. Includes tables, figures.
| Edition : | Vol. - No. |
| File Size : | 1
file |
| Note : | This product is unavailable in Ukraine, Russia, Belarus |
| Number of Pages : | 12 |
| Published : | 11/15/2004 |