Name:
3824 (RP-623) -- A Field Test Method for Determining Exhaust Rates in Grease Hoods for Commercial Kitchens (RP-623) PDF
Published Date:
1994
Status:
Active
Publisher:
ASHRAE
Describes the method, developed by correlating an average velocity measured near the filter face of the hood exhaust inlet to AMCA-210 standard measured exhaust rates. The method consists of measuring an average velocity at the filter face of the exhaust inlet and then applying a k-factor correction term to determine the exhaust rate. States the exhaust rates determined using the k-factor method are accurate to within 7% of the AMCA-210 measured reference exhaust rates.
KEYWORDS: Site testing, commercial, kitchens, exhaust hoods, measuring, air flow rate
| File Size : | 1 file , 1.3 MB |
| Note : | This product is unavailable in Russia, Belarus |
| Product Code(s) : | D-17452 |
| Published : | 1994 |