3906 (RP-680) -- Fire/Smoke Damper Study to Determine Dynamic Closure Capability and Leakage Performance PDF

3906 (RP-680) -- Fire/Smoke Damper Study to Determine Dynamic Closure Capability and Leakage Performance PDF

Name:
3906 (RP-680) -- Fire/Smoke Damper Study to Determine Dynamic Closure Capability and Leakage Performance PDF

Published Date:
1995

Status:
Active

Description:

Publisher:
ASHRAE

Document status:
Active

Format:
Electronic (PDF)

Delivery time:
10 minutes

Delivery time (for Russian version):
200 business days

SKU:

Choose Document Language:
$4.8
Need Help?

Describes a laboratory study to evaluate the capability of curtain fire dampers and multiblade fire/smoke dampers to close at air velocities and closure pressures at the ambient and elevated temperatures that may occur in smoke management systems. All dampers were UL 555 dynamically rated for closure. Most of the curtain fire dampers did not close properly at their labelled dynamic UL rating and, at elevated temperatures, the closure failure rate increased significantly. Most of the multiblade fire/smoke dampers closed at their labelled dynamic UL rating at 70degF as well as at temperatures up to 450degF. Gives the result of tests of the leakage of multiblade fire/smoke dampers at elevated temperatures after dynamic closure.

KEYWORDS: year 1995, Laboratory testing, fire dampers, multileaf fire dampers, reliability, leaking