4182 -- T-Method Duct Design, Part V: Duct Leakage Calculation Technique and Economics PDF

4182 -- T-Method Duct Design, Part V: Duct Leakage Calculation Technique and Economics PDF

Name:
4182 -- T-Method Duct Design, Part V: Duct Leakage Calculation Technique and Economics PDF

Published Date:
1998

Status:
Active

Description:

Publisher:
ASHRAE

Document status:
Active

Format:
Electronic (PDF)

Delivery time:
10 minutes

Delivery time (for Russian version):
200 business days

SKU:

Choose Document Language:
$4.8
Need Help?

The procedure of incorporating duct leakage into the T-method simulates leakage as an additional parallel section with zero length for each duct section. The assumption that additional air leakage creates additional system resistance is wrong. Leakage always reduces, not increases, system resistance. How fan power consumption changes due to leakage depends on the fan performance curve.

Methodology was developed to add duct leakage to the T-method previously developed for both the design and simulation of duct systems. It is shown that in most cases the sealing of ductwork is economical. Duct sealing is not recommended when electricity cost is less than 2¢/kWh and sealing cost is greater than $1.5/m2. A simple rule is: the higher the system cost, the greater the need for ductwork sealing.

Units: Dual


File Size : 1 file , 540 KB
Note : This product is unavailable in Russia, Belarus
Number of Pages : 6
Product Code(s) : D-7650
Published : 1998

History


Related products


Best-Selling Products

How to Start a Training Program
Published Date: 07/01/1999
$11.1