A new method for predicting local boiling coefficients of refrigerant-oil mixtures is presented. Using the refrigerant-oil mixture viscosity in place of the pure refrigerant viscosity in the recent Kattan-Thome-Favrat flow boiling model and flow pattern map without further modification predicted the R-134a/oil and R-407C/oil data quite accurately. In addition, the Friedel two-phase friction multiplier was found to work adequately for pure R-134a and pure R-407C. Finally, a new local refrigerant-oil viscosity ratio was developed that accurately predicted two-phase pressure drops of R-134a/oil and R-407C/oil mixtures at high vapor qualities.