Name:
4370 -- Velocity Decay in Air Jets for HVAC Applications PDF
Published Date:
2000
Status:
Active
Publisher:
ASHRAE
In this paper, the effect of nozzle exit velocities on the transition point between zone 3 and zone 4 (as defined in the ASHRAE Handbook) was studied for a nozzle (D = 41 mm) with different outlet velocities. Combined with the results reevaluated from Nottage (1951) and Malmström et al. (1992), the measurement results show that for air jets with Uo < 10 m/s, the end centerline velocities of zone 3 could be proportional to the outlet velocities. For air jets with Uo > 10 m/s, the end centerline velocities are relatively constant, and this tendency seems to be independent of the outlet size. Some measurement results for zone 4 are also presented.
Units: SI
| File Size : | 1 file , 360 KB |
| Note : | This product is unavailable in Russia, Belarus |
| Number of Pages : | 7 |
| Product Code(s) : | D-7201 |
| Published : | 2000 |