AB-10-006 -- An Experimental Evaluation of HVAC-Grade Carbon Dioxide Sensors—Part 4: Effects of Ageing on Sensor Performance PDF

AB-10-006 -- An Experimental Evaluation of HVAC-Grade Carbon Dioxide Sensors—Part 4: Effects of Ageing on Sensor Performance PDF

Name:
AB-10-006 -- An Experimental Evaluation of HVAC-Grade Carbon Dioxide Sensors—Part 4: Effects of Ageing on Sensor Performance PDF

Published Date:
2010

Status:
Active

Description:

Publisher:
ASHRAE

Document status:
Active

Format:
Electronic (PDF)

Delivery time:
10 minutes

Delivery time (for Russian version):
200 business days

SKU:

Choose Document Language:
$4.8
Need Help?

This is the fourth paper in a four-part series reporting on the test and evaluation of typical wall-mounted carbon-dioxide sensors used in building HVAC applications. Fifteen models of NDIR HVAC-grade wall-mounted CO2 sensors were tested and evaluated to determine the effect of ageing on the sensors’ performance. In all, 45 sensors were evaluated: three from each of the 15 models. Among the 15 models tested, eight models have a single-lamp, single-wavelength configuration, four models have a dual-lamp, single-wavelength configuration, and three models have a single-lamp, dual-wavelength configuration. All single-lamp, single-wavelength sensors and one single-lamp, dual-wavelength sensor incorporate an “automatic baseline adjustment” algorithm in the sensor’s electronics package.

Each sensor was tested under “as received” conditions, and then, over the course of one year, performance tests were conducted at four-month intervals. All tests were conducted at 40% relative humidity, 73oF (22.8oC) temperature, 14.70 psia (101.35 kPa) pressure, and 1100 ppm CO2 concentration. For each sensor, the readings from the four tests were compared in order to evaluate the effect of continuous operation on the sensor’s performance. The test results showed a wide variation in sensor performance among the various manufacturers. In one year, the maximum deviation in a sensor’s reading was observed to be 420 ppm (38%) while the minimum deviation in a sensor’s reading was observed to be 0 ppm.


File Size : 1 file , 5 MB
Note : This product is unavailable in Russia, Belarus
Number of Pages : 12
Product Code(s) : D-AB-10-006
Published : 2010

History


Related products


Best-Selling Products

IETF 8254-2
Published Date: 07/01/2016
Papiers et cartons - Mesurage du brillant spéculaire - Partie 2: Brillant à 75° avec un faisceau parallèle, méthode DIN
$24.3
IETF FAA AC 43-10
Published Date: 02/01/1983
MECHANICAL WORK PERFORMED ON U.S. AND CANADIAN REGISTERED AIRCRAFT
IETF RFC 1000
Published Date: 08/01/1987
The Request for Comments Reference Guide
$21
IETF RFC 1002
Published Date: 03/01/1987
PROTOCOL STANDARD FOR A NetBIOS SERVICE ON A TCP/UDP TRANSPORT: DETAILED SPECIFICATIONS
$18.3
IETF RFC 1014
Published Date: 06/01/1987
XDR: EXTERNAL DATA REPRESENTATION STANDARD
IETF RFC 1042
Published Date: 02/01/1988
A Standard for the Transmission of IP Datagrams over IEEE 802 Networks
$10.2