AT-84-04-2 -- Comparison of Field Performance of a High-Efficiency Heat Pump with and without a Desuperheater Water Heater PDF

AT-84-04-2 -- Comparison of Field Performance of a High-Efficiency Heat Pump with and without a Desuperheater Water Heater PDF

Name:
AT-84-04-2 -- Comparison of Field Performance of a High-Efficiency Heat Pump with and without a Desuperheater Water Heater PDF

Published Date:
1984

Status:
Active

Description:

Publisher:
ASHRAE

Document status:
Active

Format:
Electronic (PDF)

Delivery time:
10 minutes

Delivery time (for Russian version):
200 business days

SKU:

Choose Document Language:
$4.8
Need Help?

An air-to-air heat pump (COP = 3.11 at 47°F [8.3°C]) run alternately with an electric-resistance water heater and a desuperheater water heater was tested under field conditions at a site near Knoxville, TN. Results from these tests indicate that the desuperheater system has an annual performance factor (measured over a six-month period consisting of three winter and three summer months) 14 percent better than that of the system using electric resistance water heating. An analytical model predicts a 21 percent improvement over an entire year with average weather for the desuperheater system. The simple payback period ranges from seven years (for a 21 percent improvement) to about nine years (for a 14 percent improvement).


File Size : 1 file , 1.3 MB
Note : This product is unavailable in Russia, Belarus
Number of Pages : 10
Product Code(s) : D-AT-84-04-2
Published : 1984