AT-90-01-3 -- Transient Response of Fixed-Area Refrigerant Expansion Devices PDF

AT-90-01-3 -- Transient Response of Fixed-Area Refrigerant Expansion Devices PDF

Name:
AT-90-01-3 -- Transient Response of Fixed-Area Refrigerant Expansion Devices PDF

Published Date:
1990

Status:
Active

Description:

Publisher:
ASHRAE

Document status:
Active

Format:
Electronic (PDF)

Delivery time:
10 minutes

Delivery time (for Russian version):
200 business days

SKU:

Choose Document Language:
$4.8
Need Help?

A test set-up is described and data have been obtained on the response of a capillary tube and a plug orifice to a step change in refrigerant flow conditions. The transient data exhibited response times on the order of 3 to 5 minutes for the capillary tube and 30 to 40 seconds for the plug orifice. The effects of these differing response times on the transient response of a complete system may or may not be insignificant. They are not considered at this time.

KEYWORDS: refrigerants, plugs, capillary tubes, orifices, tubes, R22.


File Size : 1 file , 390 KB
Note : This product is unavailable in Russia, Belarus