CH-18-C063 -- Performance of Low GWP Refrigerant R-516A in an Air-Cooled Chiller PDF

CH-18-C063 -- Performance of Low GWP Refrigerant R-516A in an Air-Cooled Chiller PDF

Name:
CH-18-C063 -- Performance of Low GWP Refrigerant R-516A in an Air-Cooled Chiller PDF

Published Date:
2018

Status:
Active

Description:

Publisher:
ASHRAE

Document status:
Active

Format:
Electronic (PDF)

Delivery time:
10 minutes

Delivery time (for Russian version):
200 business days

SKU:

Choose Document Language:
$4.8
Need Help?

Many HFC refrigerants have a high global warming potential (GWP), and therefore have the potential to contribute to climate change. Increasing concern due to the presence of greenhouse gases, including high GWP refrigerants, in the atmosphere and their effect on global climate is leading to international policies aimed at phasing down the use of refrigerants with high global warming potentials. The HVAC&R industry is actively developing new environmentally friendly alternatives to replace the high GWP fluids currently in use. R-134a has been widely used in medium pressure refrigerant products, including medium and large capacity chillers, as the replacement for R-12. However, because of R-134a’s high GWPAR5 of 1300, the US EPA, through its Significant New Alternatives Program (SNAP) program, has placed a ban on the use of R-134a in chillers beginning in 2014. R-516A, also known as ARM-42, has been proposed as an alternative to R-134a. R-516A is an azeotropic blend of mostly R-1234yf (77.5%wt) with some R-134a (8.5%wt) and R-152a (14%wt) that has thermodynamic characteristics very similar to R-134a. R-516A has a significantly lower GWPAR5 of 130.

However, it is mildly flammable, receiving an ASHRAE Standard 34 classification of A2L. Thermodynamic calculations predict that the capacity should be 1.7% lower and the efficiency should be 2.1% lower for R-516A compared to R-134a when operating at conditions typical of the AHRI Standard 550/590 rating point. This paper describes the thermodynamic characteristics of R-516A and reports the results of tests that were performed on a 105 RT (370 kW) air cooled screw chiller with R-134a and R-516A. Performance was measured over a range of ambient air temperatures from 65°F to 125°F (18°C to 52°C). At the AHRI Standard 550/590 rating conditions, measured capacity when running the unit with R-516A was about 2% lower and EER was reduced by 3.5% to 4.0% compared to R-134a. Given these results, R-516A can be considered a design compatible alternative to R-134a in water chiller products.


File Size : 1 file , 660 KB
Note : This product is unavailable in Russia, Belarus
Number of Pages : 8
Product Code(s) : D-CH-18-C063
Published : 2018
Units of Measure : Dual

History


Related products


Best-Selling Products

SN-ISO/TS 10993-19:2006
Published Date: 07/01/2014
Biological evaluation of medical devices — Part 19: Physico-chemical, morphological and topographical characterization of materials
SN-ISO/TS 10993-19:2020
Published Date: 12/14/2020
Biological evaluation of medical devices — Part 19: Physico-chemical, morphological and topographical characterization of materials
SN-ISO/TS 10993-20:2006
Published Date: 07/01/2014
Biological evaluation of medical devices — Part 20: Principles and methods for immunotoxicology testing of medical devices
SN-ISO/TS 14067:2013
Published Date: 07/01/2013
Greenhouse gases — Carbon footprint of products — Requirements and guidelines for quantification and communication
SN-ISO/TS 14092:2020
Published Date: 09/02/2021
Adaptation to climate change - Requirements and guidance on adaptation planning for local governments and communities
SN-ISO/TS 14812:2022
Published Date: 09/20/2023
Intelligent transport systems - Vocabulary