Name:
Impact of Building Airtightness on Heat Generator and Heat Emission Equipment Sizing PDF
Published Date:
2022
Status:
Active
Publisher:
ASHRAE
The BBRI investigated the infiltration rates, using CONTAM simulations on some typical dwellings. This paper presents the results of these simulations, and reports on various dwelling properties, influencing the actual infiltration rate, among others: the infiltration rate at 50 Pa, the ventilation system, the distribution of leaks over the building envelope, the variable temperature and wind conditions, even in a small country as Belgium, the shielding of the building, height and orientation. 2 important conclusions will be reported on: first the leak infiltration ratio at room scale can be much higher than at building scale, and third; because the actual leak infiltration is mainly wind-driven and the strongest winds in Belgium occur at higher outdoor temperatures (and not the lowest design temperature) in some building configurations the biggest heat load doesn’t occur at the lowest design temperature, but at somewhat higher temperatures.
| File Size : | 1 file , 1.2 MB |
| Note : | This product is unavailable in Russia, Belarus |
| Number of Pages : | 8 |
| Product Code(s) : | D-IAQ2020-C2-C37 |
| Published : | 2022 |