Name:
MN-00-02-3 -- GSHP Bore Field Performance Comparisons of Standard and Thermally Enhanced Grout PDF
Published Date:
2000
Status:
Active
Publisher:
ASHRAE
The ability to improve the heat transfer rate of a borehole can reduce the overall bore length requirements, resulting in lower system cost. An ability to seal the borehole with grout having a higher thermal conductivity is touted as a means to reduce ground heat exchanger length. The performance in an actual GSHP system of the heat transfer of standard bentonite grout and thermally enhanced grout has been monitored. Results show a 10% improvement in instantaneous heat transfer rate with 25% more integrated total heat exchange with the enhanced grout circuit.
Units: Dual
| File Size : | 1 file , 200 KB |
| Note : | This product is unavailable in Russia, Belarus |
| Number of Pages : | 5 |
| Product Code(s) : | D-7243 |
| Published : | 2000 |