The article, “Natatoriums: The Inside Story” by Lan Xie, Ph.D., and Kenneth Cooper, Ph.D., in the April issue, was among the best I’ve seen in many years. I’d like to offer two supplemental items. First, for package refrigeration-based dehumidification systems, it is advisable to provide an auxiliary condensing unit. In warmer weather, not enough heat can be rejected into the natatorium air and pool water without raising the temperature of both.