Presents a study which questions a basic assumption regarding office plug loads (electrical equipment loads), which account for 15% to 20% of an office cooling load. Most designers assume 2 to 5 watts per ft
2 (21.5 to 53.8 W/m
2) for office equipment. Presents data from 44 office buildings selected as being typical, which shows that office electrical equipment loads are actually 1.1 watts per ft
2 (11 W/m
2). Notes a trend for these loads to decrease from now until about 2002. Notes that even in very equipment-intensive settings such as commodity trading floors, plug loads have been measured at 3 W/ft
2 (32.3 W/m
2) rather than the 8 to 10 W/ft
2 (86.1 to 107.6 W/m
2 specified).
| File Size : | 1
file
, 320 KB |
| Note : | This product is unavailable in Russia, Belarus |
| Number of Pages : | 4 |
| Product Code(s) : | D-9197 |
| Published : | 1997 |