Name:
CH-99-03-2 (RP-751) -- Effects of Oil on Boiling R-123 and R-134a Flowing Normal to an Integral-Finned Tube Bundle PDF
Published Date:
1999
Status:
Active
Publisher:
ASHRAE
Local, experimental heat transfer coefficients have been measured for boiling refrigerant flowing up and across a tube bundle segment representing a full flooded evaporator tube bundle. R-123 and R-134a data with 26 fins per inch (1024 fins per meter) tubes have been obtained. The refrigerant enters at 15% vapor quality and exits at nearly 100% vapor in order to simulate an actual flooded evaporator bundle. The nominal area heat flux was varied from 2,607 to 10,427 Btu/h·ft2 (8,224 to 32,893 W/m2 ) as the tube bundle oil content ranged from 0 to 15% (by weight) for each refrigerant/tube combination. The performance of R-22 without oil has also been determined. Local tube and bulk fluid temperatures were measured directly by thermocouples to calculate the refrigerant-side heat transfer coefficients. The bundle segment saturation temperature set point (taken at the top of the tube bundle) is 40°F (4.4°C).
Units: Dual
| File Size : | 1 file , 490 KB |
| Note : | This product is unavailable in Russia, Belarus |
| Number of Pages : | 11 |
| Product Code(s) : | D-7562 |
| Published : | 1999 |