Name:
HO-18-C065 -- Comparison of Cooling Load Between Radiant Slab and Air Systems in Large Space Buildings with Solar Radiation PDF
Published Date:
2018
Status:
Active
Publisher:
ASHRAE
In this study, through a harmonic method, we derive the analytical solution of the dynamic cooling load for a radiant slab system and air system in a largespace building with high-intensity solar radiation. The results indicate that peak value of the cooling load of a radiant system in a 24h operation isslightly larger than the air system because the conventional slab floor has a larger decay rate and time lag for the direct solar radiation than the radiantslab. However, the cooling load difference between the two systems is less than 10 W/m2 (3.17 Btu/ft2h).
| File Size : | 1 file , 730 KB |
| Note : | This product is unavailable in Russia, Belarus |
| Number of Pages : | 9 |
| Product Code(s) : | D-HO-18-C065 |
| Published : | 2018 |
| Units of Measure : | Dual |